Construction
Conductor
- Class B stranded uncoated copper conductor.
InsulationXLP crosslinked polyethylene insulation, surface print phase identification (black and numbered).
Cabling
- Three insulated conductors twisted with a class B stranded uncoated copper grounding conductor and suitable fillers, cable tape.
Jacket
- Black PVC jacket overall, surface printed.
Applications
- As flame-retardant three conductor power cables rated 600 volts, 90° C in wet or dry locations. Specifically approved for installation in cable trays per Article 340 of the NEC. Type TC cables are approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Approvals
- Listed by UL as type TC tray cable per Article 340 of the NEC.
- Individual conductors UL listed as type XHHW-2.
- Overall jacket UL listed as sunlight resistant.
- Cables pass UL and IEEE- 383 ribbon burner flame tests.
- Cables UL listed for direct burial.
- Cables meet requirements of ICEA pub. no. S-66-524 and NEMA pub. no. WC7 for crosslinked polyethylene insulated wire and cable.