Construction

Conductors:

  • Stranded soft bare copper.

Insulation:

  • Concentric layer of 90°C cross linked polyethylene (XLP). This XLP compound is specially formulated to provide excellent electrical and physical properties. Each insulated conductor passes the UL VW-1 vertical flame test.

Color Code:

  • The individual conductors are color coded in accordance with ICEA Table K-2.

Cabling:

  • The specified number of conductors are cabled with fillers where needed and a suitable tape is applied over the assembly. Two-conductor cables are flat parallel design.

Overall Jacket:

  • A heavy-duty polyvinyl chloride (PVC) sheath to meet the requirements of UL Class-12 is applied over the assembled core.

Application:

  • Control applications where cable is used in conduit, ducts, trays or racks. It can also be used in free air when supported by a messenger or for direct burial. Can be installed in cable trays per NEC Articles 318, 340 and 501.

Features:

  • Moisture and sunlight resistant.
  • Meets UL 1277 flame tray test with 70,000 BTU flame source.
  • Rated 90°C Dry, 75°C Wet, 600 volt.
  • UL Listed as type TC and for aerial use and direct burial.
  • Insulated conductors are XHHW-2 type and pass VW-1 flame test
  • Meets appropriate sections of NEC Articles 318, 340 and 501.

Meets NEC:

  • Article 318 for Cable Tray Installations.
  • Article 340 for Cable Construction.
  • Article 501 for Class 1, Div. 2 Hazardous Locations.


AttributeValue
Item #9558
Item NameXHHW-2 Tray Cable Unshielded TYPE TC 90°C WET & DRY - 600V
Size (AWG/MCM)14
No. of Conductors20
Nominal Weight(LBS/MFT)480