15268, Service Entrance Type SE, Style R-Copper, 600 V

15268, Service Entrance Type SE, Style R-Copper, 600 V

Category
Construction Conductor:
  • Fully annealed class B copper per ASTM B-3 and ASTM B-8 or B-787.
Insulation:
  • Color coded PVC (polyvinyl chloride) with a nylon jacket per UL 83 for Type THHN/THWN.
Conductor Identification:
  • Base colored insulation black, white, red.
Bare Conductor:
  • Stranded bare ground.
Tape:
  • Fiberglass reinforced binder tape.
Jacket:
  • Gray PVC (polyvinyl chloride).
Applications:
  • Above ground service entrance, panel feeder in multiple dwellings, range and dryer and other branch circuits.
  • Maximum operating temperature of phase conductors not to exceed 90°C for dry locations or 75°C for wet locations.
  • 600 volts, approved for use as specified by the NEC®.
Features:
  • Color coded phase conductors.
  • Single ground wire, not segmented.
  • Fiberglass reinforced tape under the outer jacket.
  • Sunlight and moisture resistant, flame retardant jacket.
Industry Approvals:
  • UL Standard 854.
  • Federal Specification JC-30B
  • NEC® Articles 230, 310 and 338 (NFPA 70).
Packaging:
  • 500, 1000 ft. reels
AttributeValue
Item #15268
Item Name15268, Service Entrance Type SE, Style R-Copper, 600 V
Size (AWG/MCM) 3/0-3
Strands 19
Ground Wire Size AWG 1/0
Overall Diameter (inches) 1.47
Shipping Weight (LBS/MFT) 2185
Voltage rating (volts) 600
Type Type SE Style R




    Product Enquiry