29300, Aluminum URD Cable- 600V- Triplex 90°C For Direct Burial

29300, Aluminum URD Cable- 600V- Triplex 90°C For Direct Burial

Category
Construction Conductor:
  • Compact stranded 8000 series aluminum alloy.
Insulation:
  • Crosslinked polyethylene (XLPE).
  • Type USE- 2.
Conductor Identification:
  • Black phase conductors.
  • Triple yellow striped neutral.
Construction:
  • Multiplexed cable conductors with a left hand lay in triplex (3 conductor) assembly.
Application:
  • Underground distribution from a supply source to the service entrance equipment of a building.
  • Maximum operating temperature of 90°C in dry and wet locations.
  • Direct burial application or in ducts.
  • 600 volts.
Industry Standards:
  • UL Standard 854.
  • ICEA S-66-524.
  • REA approved.
AttributeValue
Item #29300
Item Name29300, Aluminum URD Cable- 600V- Triplex 90°C For Direct Burial
Code Name Vassar
Phase Conductor-Size (AWG) 4
Strands 7
Phase Conductor Insulation (mils) 60
Neutral Conductor Size (AWG) 4
Neutral conductor stranding 7
Neutral Insulation (mils) 60
Nominal O.D. (inches) 0.754
Allowable Ampacity-Direct Burial (Amps) 125
Allowable Ampacity-In Duct (Amps) 90
Shipping Weight (MFT) 203
Phase conductor size awg 4
Allowable ampacity direct burial amps 125
Allowable ampacity duct amps 90
Temperature rating drywet 90 °C
Type Triplex
Voltage rating (volts) 600