15109, Direct Burial Building Wire Type USE-2 RHW-2 OR RHH XLP Insulation, 600V

15109, Direct Burial Building Wire Type USE-2 RHW-2 OR RHH XLP Insulation, 600V

Direct Burial Building Wire Type USE-2 RHW-2 OR RHH XLP Insulation, 600V
Category
Construction Conductor:
  • Annealed copper conductor, XLP thermosetting chemically crosslinked polyethylene insulation, surface printed.
Applications:
  • For lighting and power applications in accordance with the NEC and for other general purpose wiring applications.
  • Suitable for use in circuits not exceeding 600 volts at conductor temperatures not exceeding 90°C in wet or dry locations.
  • May be installed in raceway, duct, direct burial and aerial installations.
Industry Approvals:
  • Listed by UL as type USE-2 (90°C wet or dry) per Standard 854 for Service Entrance Cables.
  • Listed by UL as types RHW-2 (90°C wet or dry) or RHH (90°C dry) per Standard 44.
  • Conforms to ICEA Pub. No. S-66-524, utilizing column a Insulation thicknesses.
  • Conforms to Federal Specification J-C-30B.
  • Sizes 12-4 AWG stranded copper approved under FAA Advisory Circular 150/5345-7D per Spec L-824 Airport Lighting Cable, type C.
AttributeValue
Item #15109
Item Name15109, Direct Burial Building Wire Type USE-2 RHW-2 OR RHH XLP Insulation, 600V
Size (AWG/MCM) 1/0
Strands 19
Nominal Insulation Thickness (inches) 0.080
Nominal O.D. (inches) 0.530
Current- 90°C (amps) 170
Current- 75°C (amps) 150
Nominal Weight (LBS/MFT) 405
Voltage rating (volts) 600
Insulation Type XLP