22703, EPR-HYP Power Cable- 3 Conductor w/ Ground, 4 Conductor w/o Ground Type TC

22703, EPR-HYP Power Cable- 3 Conductor w/ Ground, 4 Conductor w/o Ground Type TC

cable
Category
Construction Conductors:
  • Coated, annealed copper ASTM B-189.
  • Concentric stranded, class B ASTM B-8 and UL-44 paragraph 5,1 (An opaque separator is applied between the conductor and insulation to facilitate stripping) Grounding conductor (where applicable) uncoated annealed copper class B stranding.
Insulation:
  • EPR Insul. VW1.
  • Thickness per UL-44 table 15.3 and ICEA S-68-516 part 3 table 3-1 column B.
Cabling:
  • Three and four conductors are assembled round with flame resistant, non-hygroscopic and non-wicking neoprene fillers as needed. A flame resistant, non-hygroscopic and non-wicking tape binder is applied over the assembly. Three conductor cables are cabled with a grounding conductor.
Overall Jacket:
  • Heavy duty, flame and sunlight resistant black VW1 hypalon® per UL-1277 table 10,1
Color Coding:
  • Black insulation with ICEA method 4 printed color black.
Scope:
  • Cables conform to article 318 "cable trays" and article 340 "power and control cables type TC" of the 1981 NEC, subject 1277 of UL, and ICEA S-66-524; and meet the requirements of the 70,000 BTU "cable tray propagation test" per IEEE-383, cables show reserve capabilities by also passing the 210,000 BTU flame test.
Application:
  • UL listed and OSHA acceptable.Recognized for use in Class 1, Division 2 hazardous locations and for installation in trays, wireways, troughs, channels, ducts, conduit and aerially where supported by a messenger. Specifically approved for direct burial, wet or dry locations and outdoors in cable trays where a sunlight resistant rating is required. Designed to supply power to motors, or for connections to other power devices.
AttributeValue
Item #22703
Item Name22703, EPR-HYP Power Cable- 3 Conductor w/ Ground, 4 Conductor w/o Ground Type TC
Size (AWG/MCM) 2
Strands 7
No conductors 3
Grounding cdr 6
Nominal Insulation Thickness (inches) 0.045
Nominal Jacket Thickness (inches) 0.080
Nominal O.D. (inches) 1.010
Nominal Weight (LBS/MFT) 956