25055, EPR-PVC (5000/ 8000V Shielded) Type MV-105 Power Cable- Sunlight Resistant, CT USE

25055, EPR-PVC (5000/ 8000V Shielded) Type MV-105 Power Cable- Sunlight Resistant, CT USE

cable
Category
Construction Conductor:
  • Annealed copper conductor.
Insulation:
  • Extruded conductor shield, EPR ethylene-propylene-rubber insulation, extruded insulation shield, 0.005 inch copper shielding tape.
Jacket:
  • Black polyvinyl chloride jacket, surface printed.
Application:
  • Medium voltage MV-90 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 5000 volts 133% insulation level or 8000 volts 100% insulation level, at conductor temperatures not exceeding 90°C for normal, 130°C for emergency overload and 250°C for short-circuit conditions. Suitable for installation in conduit, tray, trough, ducts, aerial and direct burial applications.
Approvals:
  • Conforms to AEIC CS6 for ethylene propylene rubber Insulated shielded power cables.
  • Conforms to ICEA pub. no. S-68-516, NEMA pub. no. WC8 for ethylene-propylene rubber- insulated wire and cable.
  • Listed by UL as type MV-90, per standard 1072.
  • Listed by UL as sunlight resistant.
  • Sizes 1/0 and larger UL listed for CT use.
  • Conforms to federal specification J-C-30B.
AttributeValue
Item #25055
Item Name25055, EPR-PVC (5000/ 8000V Shielded) Type MV-105 Power Cable- Sunlight Resistant, CT USE
Size (AWG/MCM) 1/0
Strands 19
Nominal Insulation Thickness (inches) 0.115
Nominal Jacket Thickness (inches) 0.080
Nominal O.D. (inches) 0.930
Current-Tray (Amps) 260
Current-Conduit (Amps) 180
Current-Duct (Amps) 195
Nominal Weight (LBS/MFT) 660
Current tray amps 260
Current conduit amps 180
Current duct amps 195
Voltage rating (volts) 50008000
Insulation Type EPR PVC
Shielded Yes
No conductors 1



    Product Enquiry