25109, EPR-PVC (15000V Grounded, Shielded) Type MV90 Power Cable- 100 % Insulation Level

25109, EPR-PVC (15000V Grounded, Shielded) Type MV90 Power Cable- 100 % Insulation Level

cable
Category
Construction Conductor
  • Annealed copper conductor.
Insulation
  • Extruded conductor shield, EPR ethylene propylene rubber insulation, extruded insulation shield, No. 22 AWG metallic wire shielding or copper shielding tape.
Jacket
  • Black polyvinyl chloride jacket, surface printed.
Application
  • As medium voltage MV-90 power cable for use in main feeder, distribution and branch circuits in industrial, commercial and electric utility installations. Cables may be used in wet or dry locations in circuits not exceeding 15000 volts 100% insulation level, at conductor temperatures not exceeding 90°C for normal, 130°C for emergency overload and 250°C for short circuit conditions. Suitable for installation in conduit, tray, trough, ducts, aerial and direct burial applications.
Approvals
  • Conforms to AEIC CS6 for ethylene propylene rubber Insulated shielded power cables,
  • Conforms to ICEA pub. no.S-68-516 and NEMA pub. no. WC8 for ethylene-propylene-rubber-insulated wire and cable.
  • Listed by UL as Type MV-90, per standard 1072.
  • Listed by UL as sunlight resistant.
  • Sizes 1/0 and larger UL listed for CT use.
  • Conforms to federal specification J-C-30B.
 
AttributeValue
Item #25109
Item Name25109, EPR-PVC (15000V Grounded, Shielded) Type MV90 Power Cable- 100 % Insulation Level
Size (AWG/MCM) 500
Strands 37
Nominal Insulation Thickness (inches) 0.175
Nominal Jacket Thickness (inches) 0.080
Nominal O.D. (inches) 1.580
Current-Tray (Amps) 685
Current-Conduit (Amps) 480
Current-Duct (Amps) 465
Nominal Weight (LBS/MFT) 2215
Current tray amps 685
Current conduit amps 480
Current duct amps 465
Voltage rating (volts) 15000
Insulation Type EPR
Shielded Yes
No conductors 1



    Product Enquiry