13400, XLP Power Cable- 5,000V (Unshielded) Type MV-90

13400, XLP Power Cable- 5,000V (Unshielded) Type MV-90

cable
Category
Construction Conductor:
  • Annealed uncoated copper conductor, conductor shield.
Insulation:
  • XLP black thermosetting chemically crosslinked polyethylene insulation, surface printed.
Application:
  • Where NEC jurisdiction applies as 5,000 volt non-shielded power cable, Type MV-90 Dry, for use at conductor temperatures not exceeding 90°C in dry locations. Cables meet requirements of Article 310-6 of the NEC.
  • For other applications, as non-shielded power cables for use at 5000 volts 100% insulation level (common system voltage 4160 volts) or 3000 volts 133% insulation level (common system voltage 2400 volts), under the following conditions:
    1. Single conductors mounted on insulators in free air in indoor or outdoor locations.
    2. Random lay singles in metal conduit or triplexed singles in non-metallic conduit, above grade, in dry locations.
    3. Single conductors or triplexed singles, aerially, field-spun to grounded messenger in dry, damp or wet locations.
    4. Triplexed singles in trays, in spaced block supports or in messenger supported rings, indoors above grade in dry locations.
Approvals:
  • Listed by UL as 5,000 volt non- shielded cable, type MV-90 dry, per UL standard 1072.
  • Conforms to ICEA pub. no. S-66-524 and NEMA pub. no. WC7 for crosslinked- thermosetting-polyethylene-insulated wire and cable.
  • Sizes 8-4 AWG with copper conductor approved under FAA AC 150/5345 7D, specification L-824 underground electrical cable for airport lighting circuits type C
AttributeValue
Item #13400
Item Name13400, XLP Power Cable- 5,000V (Unshielded) Type MV-90
Size (AWG/MCM) 8
Strands 7
Nominal Insulation Thickness (inches) 0.110
Nominal O.D. (inches) 0.390
Current-Conduit (Amps) 55
Currentair amps 83
Nominal Weight (LBS/MFT) 90
Current conduit amps 55
Current air amps 83