25030, Type MV90 – Wet or Dry Unshielded EPR/XL-CPE 2400 Volt

25030, Type MV90 – Wet or Dry Unshielded EPR/XL-CPE 2400 Volt

cable
Category
Conductor:
  • Class B stranded annealed uncoated copper. Conductors shall be covered with a thermostat semi conduction stress control layer over conductor.
Insulation:
  • EPR (ethylene propylene rubber)
Jacket:
  • Lead free cross-linked chorinated polyethyline (XL-CPE)
Application:
  • Where NEC juisdiction applies; as 2,400-volt nonshielded power cable, Type MV-90, for use at conductor temperatures not exceeding 90ºC in wet or dry locations. Cables meet requirements of Article 310.6 of the National Electrical Code.
  • For use in aerial, conduit, open tray and underground duct installations.
  • Excellent heat and moisture resistance.
  • Low moisture absorption.
  • High dielectric strength.
  • Low dielectric loss.
  • Chemical and sunlight resistant.
  • Meets cold bend test at -35ºC.
Industry Approvals:
  • Listed by UL as 2,400 volt nonshielded cable, Type MV-90, per UL Standard 1072.
  • Conforms to ICEA S-96-659/NEMA WC71.
  • Sizes 1/0 AWG and larger pass UL and IEEE Standard 383 ribbon burner flame test and are UL listed for CT Use.
AttributeValue
Item #25030
Item Name25030, Type MV90 – Wet or Dry Unshielded EPR/XL-CPE 2400 Volt
Size (AWG/MCM) 6
Strands 7
Nominal Insulation Thickness (inches) 0.125
Nominal Jacket Thickness (inches) 0.080
Nominal O.D. (inches) 0.62
Nominal Weight(LBS/MFT) 241